Haier - Test-Report
Pubblicazione animata
Test Report
Report No. ........................ :
AHES231000138671
Issued date ............. :
2023-10-27
Split Type Room Air Conditioner
AS35XCAHRA / 1U35S2SM1FA-2
Product Description......... :
Model No................. :
Date of Sample Received. :
2023-05-19
No. of samples.. : 1
Date of Test ...................... :
2023-05-20 to 2023-05-30
Qingdao Haier Air Conditioner General Corp., Ltd. No.1 Haier Road Hi-Tech Zone, Qingdao City, P.R. China. Qingdao Haier (JiaoZhou) Air Conditioner Co., Ltd. Haier Industry Park, Haier Road, Jiaozhou City, Qingdao, P.R. China. SGS-CSTC standards Technical Services Co., Ltd. Anhui Branch 1/F&2/F, West Building C12, Gongtou Liheng Industrial Square, Fanhua Road, Economic & Technological Development Area, Hefei, 230601 Anhui, China
Applicant .......................... :
Factory ............................. :
Laboratory that preparing the Report ………………… .:
Testing address ………… ...: Qingdao Haier Air Conditioner General Corp., Ltd.
No.1 Haier Road Hi-Tech Zone, Qingdao City, P.R. China.
Energy saving effect in ECO mode
Test Procedure................. :
Test result ........................ : Refer to page 5 and 6
Remark /Note ................... :
N/A
Photos of submitted sample:
Indoor unit
Outdoor unit
Tested By:
Approved by:
Jarvan Deng
Hunter Lin
This document is issued by the Company subject to its General Conditions of Service printed overleaf, available on request or accessible at http://www.sgs.com/en/Terms-and-Conditions.aspx and, for electronic format documents, subject to Terms and Conditions for Electronic Documents at http://www.sgs.com/en/Terms-and-Conditions/Terms-e-Document.aspx. Attention is drawn to the limitation of liability, indemnification and jurisdiction issues defined therein. Any holder of this document is advised that information co ntained hereon reflects the Company’s findings at the time of its intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and thi s document does not exonerate parties to a transaction from exercising all their rights and obligations under the transaction documents. This document cannot be reproduced except in full, without prior written approval of the Company. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law. Unless otherwise stated the results shown in this test report refer only to the sample(s) tested and such sample(s) are retained for 30 days only.
Member of the SGS Group (SGS SA) TRF No. EEC_Protocol performance test B
Page 2 of 9
Report No.: AHES231000138671
Technical data:
Trademark .............................................................. : Haier
Type of appliance.................................................... : Split Type Room Air Conditioner
Type / model ........................................................... : AS35XCAHRA / 1U35S2SM1FA-2
Method of supply cord attachment............................ : Type Y
Rated Voltage(V)..................................................... : 220 V – 240 V
Rated Frequency (Hz) ............................................ : 50 Hz
Rated Cooling input................................................. : 1600 W; 7.2 A
Rated heating input ................................................. : 1600 W; 7.2 A
Refrigerant Charge.................................................. : R32/0.78 kg
IP number ............................................................... : IPX4 (outdoor unit)
Degree of protection .............................................. : Class I
TABLE: Critical components information Object
Manufacturer / Trademark
Type / Model
Compressor
Shanghai Highly Electrical Appliances Co., Ltd. GSD098RKTF6JV6B
Indoor unit fan motor Outdoor unit fan motor
Nidec Shibaura (Zhejiang) Corporation. Nidec Shibaura (Zhejiang) Corporation. Qingdao H&T Intelligent Control Technology Co., Ltd. Chearihi (Anhui) Technology Co., Ltd.
SIC-36CS-F130-6 SIC-54FM-F125-1
Indoor unit PCB
0011801123D
Outdoor unit PCB
0011801048C
Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B
Page 3 of 9
Report No.: AHES231000138671
Copy of Marking Plate
The label below may be only a draft.
Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B
Page 4 of 9
Report No.: AHES231000138671
Testing plan
1. Test sample:
Single split type room air conditioner
2. Test conditions: Mode
Indoor
Outdoor
Dry bulb temperature
Wet bulb temperature
Dry bulb temperature
Wet bulb temperature
Cooling mode Heating mode
30°C 10°C
/ /
35°C
24°C
2°C
1°C
3. Test environment: Environmental laboratory, with an area of 16.8m 2 , and a height of 3.15m, the installation height of the indoor unit is 2.3m.
4. Test Method:
Test number
Remote controller setting
Test requirements
Energy-saving ratio
1
1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: Off 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L1 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L2 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L3 1.Mode: Heating mode 2. Temperature: 19°C 3.Fan speed: High 4.ECO gear: Off 1.Mode: Heating mode 2.Temperature: 19°C 3.Fan speed: High 4.ECO gear: L1 1.Mode: Heating mode 2.Temperature: 19°C 3.Fan speed: High 4.ECO gear: L2 1.Mode: Heating mode 2.Températures: 19°C 3.Fan speed: High 4.ECO gear: L3
Tested at ECO L3 gear mode (test number 4) first, when the room average temperature reached the target temperature 26°C, stop testing and record the running time and the energy consumption. The running time of other test number (1, 2, 3) equals to the ECO L3 gear mode (test number 4), after testing, record the running time and the energy consumption. Tested at ECO L3 gear mode (test number 8) first, when the room average temperature reached the target temperature 19°C, stop testing and record the running time and the energy consumption. The running time of other test number (5, 6, 7) equals to the ECO L3 gear mode (test number 8), after testing, record the running time and the energy consumption.
Based on the test values of ECO off mode, calculate the energy saving ratio per unit time for ECO L1 gear mode, ECO L2 gear mode and ECO L3 gear mode.
2
3
4
5
6
7
8
5. Test parameters: 230V, 50Hz
Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B
Page 5 of 9
Report No.: AHES231000138671
Test result: Test No.
Remote controller setting
Test environment
Test result
Energy-saving effect
Test condition
Area (m 2 )
Installation height of the indoor unit (m)
Energy consumption (kWh)
Running time (h)
Energy consumption per unit time (kWh) 1
Energy-saving ratio (%) 2
1
1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: Off 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L1 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L2 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L3 1.Mode: Heating mode 2. Temperature: 19°C 3.Fan speed: High 4.ECO gear: Off 1.Mode: Heating mode 2.Temperature: 19°C 3.Fan speed: High 4.ECO gear: L1 1.Mode: Heating mode 2.Temperature: 19°C 3.Fan speed: High 4.ECO gear: L2 1.Mode: Heating mode 2.Températures: 19°C
Indoor:30°C/- Outdoor:35°C/24°C
0.472
0.514
0.918
/
2
0.422
0.514
0.821
10.57
3
0.335
0.514
0.652
28.98
4
0.231
0.514
0.449
51.09
16.8
2.3
5
Indoor:10°C/- Outdoor: 2°C/1°C
3.98
3.0125
1.321
/
6
3.583
3.0125
1.189
9.99
7
3.181
3.0125
1.056
20.06
8
1.892
3.0125
0.628
52.46
Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B
Page 6 of 9
Report No.: AHES231000138671
3.Fan speed: High 4.ECO gear: L3
Remark: 1.Energy consumption per unit time = energy consumption / running time 2.Cooling mode: Energy saving ratio (%) = (Energy consumption per unit time (1) - Energy consumption per unit time (*)) / Energy consumption per unit time (1) (*= test No. 2, 3 or 4) Heating mode: Energy saving ratio (%) = (Energy consumption per unit time (5) - Energy consumption per unit time (*)) / Energy consumption per unit time (5) (*= test No. 6, 7 or 8)
Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B
Page 7 of 9
Report No.: AHES231000138671
Environmental laboratory and temperature sensor:
Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B
Page 8 of 9
Report No.: AHES231000138671
Photo Documents:
Front view of outdoor unit
Front view of indoor unit
Remote controller
Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B
Page 9 of 9
Report No.: AHES231000138671
List of equipment used:
Equipments name Environmental Laboratory
Model/Type
Serial No.
Calibration
Calibration certificate No. G1912261483 001
Resolution Calibration due date
/
TQ-022A-076
CVC Testing Technology Co., Measuring Center Third Measuring & Testing Center Station Under Machinery Industry (Guangzhou)
OK
2024/04/21
*** End of Test Report ***
Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B
Made with FlippingBook Annual report maker