Haier - Test-Report

Pubblicazione animata

Test Report

Report No. ........................ :

AHES231000138671

Issued date ............. :

2023-10-27

Split Type Room Air Conditioner

AS35XCAHRA / 1U35S2SM1FA-2

Product Description......... :

Model No................. :

Date of Sample Received. :

2023-05-19

No. of samples.. : 1

Date of Test ...................... :

2023-05-20 to 2023-05-30

Qingdao Haier Air Conditioner General Corp., Ltd. No.1 Haier Road Hi-Tech Zone, Qingdao City, P.R. China. Qingdao Haier (JiaoZhou) Air Conditioner Co., Ltd. Haier Industry Park, Haier Road, Jiaozhou City, Qingdao, P.R. China. SGS-CSTC standards Technical Services Co., Ltd. Anhui Branch 1/F&2/F, West Building C12, Gongtou Liheng Industrial Square, Fanhua Road, Economic & Technological Development Area, Hefei, 230601 Anhui, China

Applicant .......................... :

Factory ............................. :

Laboratory that preparing the Report ………………… .:

Testing address ………… ...: Qingdao Haier Air Conditioner General Corp., Ltd.

No.1 Haier Road Hi-Tech Zone, Qingdao City, P.R. China.

Energy saving effect in ECO mode

Test Procedure................. :

Test result ........................ : Refer to page 5 and 6

Remark /Note ................... :

N/A

Photos of submitted sample:

Indoor unit

Outdoor unit

Tested By:

Approved by:

Jarvan Deng

Hunter Lin

This document is issued by the Company subject to its General Conditions of Service printed overleaf, available on request or accessible at http://www.sgs.com/en/Terms-and-Conditions.aspx and, for electronic format documents, subject to Terms and Conditions for Electronic Documents at http://www.sgs.com/en/Terms-and-Conditions/Terms-e-Document.aspx. Attention is drawn to the limitation of liability, indemnification and jurisdiction issues defined therein. Any holder of this document is advised that information co ntained hereon reflects the Company’s findings at the time of its intervention only and within the limits of Client’s instructions, if any. The Company’s sole responsibility is to its Client and thi s document does not exonerate parties to a transaction from exercising all their rights and obligations under the transaction documents. This document cannot be reproduced except in full, without prior written approval of the Company. Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law. Unless otherwise stated the results shown in this test report refer only to the sample(s) tested and such sample(s) are retained for 30 days only.

Member of the SGS Group (SGS SA) TRF No. EEC_Protocol performance test B

Page 2 of 9

Report No.: AHES231000138671

Technical data:

Trademark .............................................................. : Haier

Type of appliance.................................................... : Split Type Room Air Conditioner

Type / model ........................................................... : AS35XCAHRA / 1U35S2SM1FA-2

Method of supply cord attachment............................ : Type Y

Rated Voltage(V)..................................................... : 220 V – 240 V

Rated Frequency (Hz) ............................................ : 50 Hz

Rated Cooling input................................................. : 1600 W; 7.2 A

Rated heating input ................................................. : 1600 W; 7.2 A

Refrigerant Charge.................................................. : R32/0.78 kg

IP number ............................................................... : IPX4 (outdoor unit)

Degree of protection .............................................. : Class I

TABLE: Critical components information Object

Manufacturer / Trademark

Type / Model

Compressor

Shanghai Highly Electrical Appliances Co., Ltd. GSD098RKTF6JV6B

Indoor unit fan motor Outdoor unit fan motor

Nidec Shibaura (Zhejiang) Corporation. Nidec Shibaura (Zhejiang) Corporation. Qingdao H&T Intelligent Control Technology Co., Ltd. Chearihi (Anhui) Technology Co., Ltd.

SIC-36CS-F130-6 SIC-54FM-F125-1

Indoor unit PCB

0011801123D

Outdoor unit PCB

0011801048C

Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B

Page 3 of 9

Report No.: AHES231000138671

Copy of Marking Plate

The label below may be only a draft.

Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B

Page 4 of 9

Report No.: AHES231000138671

Testing plan

1. Test sample:

Single split type room air conditioner

2. Test conditions: Mode

Indoor

Outdoor

Dry bulb temperature

Wet bulb temperature

Dry bulb temperature

Wet bulb temperature

Cooling mode Heating mode

30°C 10°C

/ /

35°C

24°C

2°C

1°C

3. Test environment: Environmental laboratory, with an area of 16.8m 2 , and a height of 3.15m, the installation height of the indoor unit is 2.3m.

4. Test Method:

Test number

Remote controller setting

Test requirements

Energy-saving ratio

1

1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: Off 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L1 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L2 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L3 1.Mode: Heating mode 2. Temperature: 19°C 3.Fan speed: High 4.ECO gear: Off 1.Mode: Heating mode 2.Temperature: 19°C 3.Fan speed: High 4.ECO gear: L1 1.Mode: Heating mode 2.Temperature: 19°C 3.Fan speed: High 4.ECO gear: L2 1.Mode: Heating mode 2.Températures: 19°C 3.Fan speed: High 4.ECO gear: L3

Tested at ECO L3 gear mode (test number 4) first, when the room average temperature reached the target temperature 26°C, stop testing and record the running time and the energy consumption. The running time of other test number (1, 2, 3) equals to the ECO L3 gear mode (test number 4), after testing, record the running time and the energy consumption. Tested at ECO L3 gear mode (test number 8) first, when the room average temperature reached the target temperature 19°C, stop testing and record the running time and the energy consumption. The running time of other test number (5, 6, 7) equals to the ECO L3 gear mode (test number 8), after testing, record the running time and the energy consumption.

Based on the test values of ECO off mode, calculate the energy saving ratio per unit time for ECO L1 gear mode, ECO L2 gear mode and ECO L3 gear mode.

2

3

4

5

6

7

8

5. Test parameters: 230V, 50Hz

Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B

Page 5 of 9

Report No.: AHES231000138671

Test result: Test No.

Remote controller setting

Test environment

Test result

Energy-saving effect

Test condition

Area (m 2 )

Installation height of the indoor unit (m)

Energy consumption (kWh)

Running time (h)

Energy consumption per unit time (kWh) 1

Energy-saving ratio (%) 2

1

1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: Off 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L1 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L2 1.Mode: Cooling mode 2.Temperature: 26°C 3.Fan speed: High 4.ECO gear: L3 1.Mode: Heating mode 2. Temperature: 19°C 3.Fan speed: High 4.ECO gear: Off 1.Mode: Heating mode 2.Temperature: 19°C 3.Fan speed: High 4.ECO gear: L1 1.Mode: Heating mode 2.Temperature: 19°C 3.Fan speed: High 4.ECO gear: L2 1.Mode: Heating mode 2.Températures: 19°C

Indoor:30°C/- Outdoor:35°C/24°C

0.472

0.514

0.918

/

2

0.422

0.514

0.821

10.57

3

0.335

0.514

0.652

28.98

4

0.231

0.514

0.449

51.09

16.8

2.3

5

Indoor:10°C/- Outdoor: 2°C/1°C

3.98

3.0125

1.321

/

6

3.583

3.0125

1.189

9.99

7

3.181

3.0125

1.056

20.06

8

1.892

3.0125

0.628

52.46

Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B

Page 6 of 9

Report No.: AHES231000138671

3.Fan speed: High 4.ECO gear: L3

Remark: 1.Energy consumption per unit time = energy consumption / running time 2.Cooling mode: Energy saving ratio (%) = (Energy consumption per unit time (1) - Energy consumption per unit time (*)) / Energy consumption per unit time (1) (*= test No. 2, 3 or 4) Heating mode: Energy saving ratio (%) = (Energy consumption per unit time (5) - Energy consumption per unit time (*)) / Energy consumption per unit time (5) (*= test No. 6, 7 or 8)

Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B

Page 7 of 9

Report No.: AHES231000138671

Environmental laboratory and temperature sensor:

Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B

Page 8 of 9

Report No.: AHES231000138671

Photo Documents:

Front view of outdoor unit

Front view of indoor unit

Remote controller

Member of the SGS Group (SGS SA) TRF No. EEC_ Protocol performance test B

Page 9 of 9

Report No.: AHES231000138671

List of equipment used:

Equipments name Environmental Laboratory

Model/Type

Serial No.

Calibration

Calibration certificate No. G1912261483 001

Resolution Calibration due date

/

TQ-022A-076

CVC Testing Technology Co., Measuring Center Third Measuring & Testing Center Station Under Machinery Industry (Guangzhou)

OK

2024/04/21

*** End of Test Report ***