Report No.: AHES230800110871

Testing plan

1. Test sample: Single split type room air conditioner; three interchangeable special air volume indoor unit fan (85% ±3%, 80% ±3%, 65% ±3%). Special air volume fan: Add obstructions onto the fan to simulate the impact of dust accumulation on the air volume, the air volume is measured through the enthalpy different laboratory.

2. Special air volume indoor unit fan treatment: Add obstructions on the middle of fan to achieve the purpose of affecting the air volume. The associated test design, covering area (Permissible Error ±0.2%), and treated fan air volume (Permissible Error ±30) are shown in the table below:

Air volume (m 3 /h)

Test setting (Indoor unit)

Fan number

Covering area

Ratio

4# (100% air volume) 1# (85% air volume) 2# (80% air volume) 3# (65% air volume)

1.Mode: Air supply mode 2.Fan speed: High 3.Guide plate: Maximum position of air outlet

0%

670

100%

4.90%

562

83.88%

5.71%

540

80.6%

8.16%

422

62.99%

3. Test conditions: Mode

Indoor

Outdoor

Dry bulb temperature

Wet bulb temperature

Dry bulb temperature

Wet bulb temperature

Cooling mode Heating mode

30°C 10°C

/ /

35°C

24°C

2°C

1°C

4. Test environment: Environmental laboratory, with an area of 16.8m 2 , and a height of 3.15m, the installation height of the indoor unit is 2.3m.

5. Test Method:

1) Air conditioner: Test number Fan number

Air conditioner

Test requirements

Test setting

Target average room temperature

1

4# (100% air volume) 1.Mode: Cooling mode 2.Fan speed: High 3.Guide plate: Maximum position of air outlet 1# (85% air volume) 2# (80% air volume) 4# (100% air volume) 1.Mode: Heating mode 2.Fan speed: High 3.Guide plate: Maximum position of air outlet 1# (85% air volume) 2# (80% air volume) 3# (65% air volume)

22°C

Record the energy consumption when the target average room temperature is first reached, compare the energy wasting based on the

2

3

4

5

19°C

6

4# fan (100% air volume) and the

7

8

3# (65% air volume)

energy saving based on the 3# fan (65% air volume).