Report No...........................:
AHES230800110871
Issued date...............:
2023-08-24
Split Type Room Air Conditioner
AS35XCAHRA / 1U35S2SM1FA-2
Product Description. ........:
Model No. .................:
Date of Sample Received .:
2023-07-24
No. of samples...: 4
Date of Test .......................:
2023-07-25 to 2023-07-28
Qingdao Haier Air Conditioner General Corp., Ltd. No.1 Haier Road Hi-Tech Zone, Qingdao City, P.R. China. Qingdao Haier (JiaoZhou) Air Conditioner Co., Ltd. Haier Industry Park, Haier Road, Jiaozhou City, Qingdao, P.R. China. SGS-CSTC standards Technical Services Co., Ltd. Anhui Branch 1/F&2/F, West Building C12, Gongtou Liheng Industrial Square, Fanhua Road, Economic & Technological Development Area, Hefei, 230601 Anhui, China
Applicant............................ :
Factory ...............................:
Laboratory that preparing the Report ………………… .:
Testing address ………… ...: Qingdao Haier Air Conditioner General Corp., Ltd.
No.1 Haier Road Hi-Tech Zone, Qingdao City, P.R. China.
Test protocol for Energy saving effect of Easy-to-Clean product platform
Test Procedure .................. :
Test result..........................: Refer to page 6 and 7
The product meets the Enterprise Standard: Haier Q/HKT J09230-2021 Code for evaluation of easy disassembly and cleaning performance of room air conditioner
Remark /Note ....................:
Photos of submitted sample:
Indoor unit
Outdoor unit
Tested By:
Approved by:
Jarvan Deng
Hunter Lin
TRF No. EEC_Protocol performance test A
Page 2 of 11
Report No.: AHES230800110871
Technical data:
Trademark .................................................................... : Haier
Type of appliance......................................................... : Split Type Room Air Conditioner
Type / model................................................................. : AS35XCAHRA / 1U35S2SM1FA-2
Method of supply cord attachment .............................. : Type Y
Rated Voltage(V).......................................................... : 220 V – 240 V
Rated Frequency (Hz) ................................................. : 50 Hz
Rated Cooling input ..................................................... : 1600 W; 7.2 A
Rated heating input ..................................................... : 1600 W; 7.2 A
Refrigerant Charge ...................................................... : R32/0.78 kg
IP number ..................................................................... : IPX4 (outdoor unit)
Degree of protection .................................................: Class I
TABLE: Critical components information Object
Manufacturer / Trademark
Type / Model
Compressor
Shanghai Highly Electrical Appliances Co., Ltd. GSD098RKTF6JV6B
Indoor unit fan motor Outdoor unit fan motor
Nidec Shibaura (Zhejiang) Corporation. Nidec Shibaura (Zhejiang) Corporation. Qingdao H&T Intelligent Control Technology Co., Ltd. Chearihi (Anhui) Technology Co., Ltd.
SIC-36CS-F130-6 SIC-54FM-F125-1
Indoor unit PCB
0011801123D
Outdoor unit PCB
0011801048C
TRF No. EEC_Protocol performance test A
Page 3 of 11
Report No.: AHES230800110871
Copy of Marking Plate
The label below may be only a draft.
TRF No. EEC_Protocol performance test A
Page 4 of 11
Report No.: AHES230800110871
Testing plan
1. Test sample: Single split type room air conditioner; three interchangeable special air volume indoor unit fan (85% ±3%, 80% ±3%, 65% ±3%). Special air volume fan: Add obstructions onto the fan to simulate the impact of dust accumulation on the air volume, the air volume is measured through the enthalpy different laboratory.
2. Special air volume indoor unit fan treatment: Add obstructions on the middle of fan to achieve the purpose of affecting the air volume. The associated test design, covering area (Permissible Error ±0.2%), and treated fan air volume (Permissible Error ±30) are shown in the table below:
Air volume (m 3 /h)
Test setting (Indoor unit)
Fan number
Covering area
Ratio
4# (100% air volume) 1# (85% air volume) 2# (80% air volume) 3# (65% air volume)
1.Mode: Air supply mode 2.Fan speed: High 3.Guide plate: Maximum position of air outlet
0%
670
100%
4.90%
562
83.88%
5.71%
540
80.6%
8.16%
422
62.99%
3. Test conditions: Mode
Indoor
Outdoor
Dry bulb temperature
Wet bulb temperature
Dry bulb temperature
Wet bulb temperature
Cooling mode Heating mode
30°C 10°C
/ /
35°C
24°C
2°C
1°C
4. Test environment: Environmental laboratory, with an area of 16.8m 2 , and a height of 3.15m, the installation height of the indoor unit is 2.3m.
5. Test Method:
1) Air conditioner: Test number Fan number
Air conditioner
Test requirements
Test setting
Target average room temperature
1
4# (100% air volume) 1.Mode: Cooling mode 2.Fan speed: High 3.Guide plate: Maximum position of air outlet 1# (85% air volume) 2# (80% air volume) 4# (100% air volume) 1.Mode: Heating mode 2.Fan speed: High 3.Guide plate: Maximum position of air outlet 1# (85% air volume) 2# (80% air volume) 3# (65% air volume)
22°C
Record the energy consumption when the target average room temperature is first reached, compare the energy wasting based on the
2
3
4
5
19°C
6
4# fan (100% air volume) and the
7
8
3# (65% air volume)
energy saving based on the 3# fan (65% air volume).
TRF No. EEC_Protocol performance test A
Page 5 of 11
Report No.: AHES230800110871
2) Disassembly and assembly the interchangeable fan: According to user manufacturer ’ s instruction.
6. Test parameters: 220V, 50Hz
TRF No. EEC_Protocol performance test A
Page 6 of 11
Report No.: AHES230800110871
Air volume test
Test result:
Test setting (Indoor unit)
Air volume (m 3 /h)
Measured air volume (m 3 /h) 1
Fan number
4# (100% air volume) 1# (85% air volume) 2# (80% air volume) 3# (65% air volume)
1.220V, 50Hz 2.Mode: air supply mode 3.Fan speed: High 4.Guide plate: maximum position of air outlet
670
676,3
562
568,6
540
556,1
422
428,6
Remark : 1. Permissible Error ±30
TRF No. EEC_Protocol performance test A
Page 7 of 11
Report No.: AHES230800110871
Energy consumption test
Test result: Test No.
Air conditioner
Test environment
Test result
Energy-saving effect
Fan number
Air volume (m 3 /h)
Test setting
Target average room temperature
Test condition
Area (m 2 )
Installation height of the indoor unit (m)
Energy consumption (kWh)
Energy wasting (kWh)
Energy wasting ratio (%) 1
Energy saving ratio (%) 2
1
4# (100% air volume)
670
1.220V, 50Hz 2.Mode: Cooling 3.Fan speed: High 4.Guide plate: Maximum position of air outlet 1.220V, 50Hz 2.Mode: Heating 3.Fan speed: High 4.Guide plate: Maximum position of air outlet
22°C
Indoor: 30°C/- Outdoor: 35°C/24°C
0.860
/
/
30.4
2
1# (85% air volume) 2# (80% air volume) 3# (65% air volume)
562
0.968
0.108
12.6
21.7
3
540
1.106
0.246
28.6
10.5
4
422
1.236
0.376
43.7
/
16.8
2.3
5
4# (100% air volume)
670
19°C
Indoor: 10°C/-
0.897
/
/
54.1
Outdoor: 2°C/1°C
6
1# (85% air volume) 2# (80% air volume) 3# (65% air volume)
562
0.928
0.031
3.5
52.6
7
540
1.582
0.685
76.4
19.1
8
422
1.956
1.059
118.1
/
Remark: 1. Energy wasting ratio (%) = (energy consumption (*#) - energy consumption (4#)) / energy consumption (4#) (*=1, 2 or 3) 2. Energy saving ratio (%) = (energy consumption (3#) - energy consumption (*#)) / energy consumption (3#) (*=1, 2 or 4)
TRF No. EEC_Protocol performance test A
Page 8 of 11
Report No.: AHES230800110871
Environmental laboratory and temperature sensor
TRF No. EEC_Protocol performance test A
Page 9 of 11
Report No.: AHES230800110871
Photo Documents
Front view of outdoor unit
Front view of indoor unit
3# fan motor
3# fan motor
3# fan motor
3# fan motor
3# fan motor
4# fan motor
Remote controller
TRF No. EEC_Protocol performance test A
Page 10 of 11
Report No.: AHES230800110871
Photo Documents
2# fan motor
2# fan motor
2# fan motor
2# fan motor
2# fan motor
1# fan motor
1# fan motor
1# fan motor
1# fan motor
1# fan motor
TRF No. EEC_Protocol performance test A
Page 11 of 11
Report No.: AHES230800110871
List of equipment used
Equipments name Environmental Laboratory
Model/Type
Serial No.
Calibration
Calibration certificate No. G1912261483 001
Resolution Calibration due date
/
TQ-022A-076
CVC Testing Technology Co., Measuring Center Third Measuring & Testing Center Station Under Machinery Industry (Guangzhou)
OK
2024/04/21
Enthalpy Different Laboratory
5HP
TQ-022A-087 National Institute of Metrology
CLzx2023-00107
OK
2024/05/15
*** End of Test Report ***