Test Report
Report No...........................:
AHEE230300050751
Issued date...............:
2023-03-20
Single Split Type Room Air Conditioner
AS12FBAHRA, 1U12MEHFRA
Product Description. ........:
Model No. .................:
Date of Sample Received .:
2023-03-09
No. of samples...: 1
Date of Test .......................:
2023-03-09
Qingdao Haier Air Conditioner General Corp., Ltd No.1 Haier Road Hi-Tech Zone, Qingdao City, P.R. China Qingdao Haier Air Conditioner General Corp., Ltd No.1 Haier Road Hi-Tech Zone, Qingdao City, P.R. China Qingdao Haier(JiaoZhou) Air Conditioner General Corp., Ltd Haier Road Hi-Tech Zone, Jiaozhou area, Qingdao City, P.R. China SGS-CSTC Standards Technical Services Co., Ltd. Anhui Branch 1/F&2/F, West Building C12, Gongtou Liheng Industrial Square, Fanhua Road, Economic & Technological Development Area, Hefei, 230601 Anhui, China SGS-CSTC Standards Technical Services Co., Ltd. Anhui Branch 1/F&2/F, West Building C12, Gongtou Liheng Industrial Square, Fanhua Road, Economic & Technological Development Area, Hefei, 230601 Anhui, China
Applicant............................ :
Manufacturer .....................:
Factory ...............................:
Laboratory that preparing the Report:
Testing address:
Test protocol to measure the fractional energy saving
Test Procedure .................. :
Conclusion ........................: Refer to page 4&6
Remark /Note ....................:
N/A
Photos of submitted sample:
Tested By:
Approved by:
Jarvan Deng
Hunter Lin
TRF No. EEC_Protocol performance test A
Page 2 of 7
Report No.: AHEE230300050751
Technical data:
Trademark .................................................................... : Haier
Type of appliance......................................................... : Single Split Type Room Air Conditioner
Type / model................................................................. : AS12FBAHRA, 1U12MEHFRA
Method of supply cord attachment .............................. : Type Y
Rated Voltage(V).......................................................... : 220 V - 240 V; 50 Hz
Pdesign cooling capacity............................................. : 3500 W
Pdesign heating capacity ............................................ : 2800 W
Rated power input........................................................ : 1600 W; 7.2 A
Refrigerant Charge ...................................................... : R32: 0.78 kg
IP number ..................................................................... : IPX4 (outdoor unit)
Degree of protection .................................................: Class I
TABLE: Critical components information Object
Manufacturer / trademark
Type / model
Compressor
SHANGHAI HIGHLY ELECTRICAL APPLIANCES CO., LTD NIDEC SHIBAURA (Zhejiang) CORPORATION Wolong Electric (Ji nan) Motor Co., Ltd. QINGDAO YUNLU ENERGY TECHNOLOGY CO .,LTD.
GSD098RKTF6JV6B
Indoor unit fan motor Outdoor unit fan motor
SIC-310-30-1(G) WZD-A01025L-01A
Reactor
R1505HRA
TRF No. EEC_Protocol performance test A
Page 3 of 7
Report No.: AHEE230300050751
Copy of Marking Plate
The label below may be only a draft.
TRF No. EEC_Protocol performance test A
Page 4 of 7
Report No.: AHEE230300050751
Test protocol to measure the fractional energy saving
Test Details Description – Cooling mode Model
AS12FBAHRA(indoor unit) + 1U12MEHFRA(outdoor unit)
Test voltage(V)/ Test frequency(Hz)
230 V, 50 Hz
EN14511-2: 2022/ Table 4: Cooling Mode – Standard Rating Conditions; Indoor Room Size: 22.34 mm 2 ; Installation Height of Indoor Unit: 2.3 m; Indoor Room Dry Bulb( ℃ )/Wet Bulb( ℃ ) : 27/19; Outdoor Room Dry Bulb( ℃ )/Wet Bulb( ℃ ) : 35/24
Test conditions
Measurement 1 Settings
Air conditioner is set to cooling mode, the temperature is set to 16 ℃ , the wind speed is set to min.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour
Test data
Details see below table
Measurement 2 Settings
Air conditioner is set to cooling mode, the temperature is set to 16 ℃ , the wind speed is set to max.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Measurement 3 Settings
Air conditioner is set to cooling mode, the temperature is set to 26 ℃ , the wind speed is set to max.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Measurement 4 Settings
Air conditioner is set to cooling mode, the temperature is set to 26 ℃ , the wind speed is set to min.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Set to ‘ Cooling-26 ℃ - min wind ’ speed mode compared to 16 ℃ , can save the energy consumption 0.316 kwh per hour, the ration of fractional energy saving can up to 63%. Set to ‘ Cooling-26 ℃ - max wind speed ’ mode compared to 16 ℃ , can save the energy consumption 0.591 kwh per hour, the ration of fractional energy saving can up to 88%.
Comparison of measurement 1&4
Conclusion
Comparison of measurement 2&3
TRF No. EEC_Protocol performance test A
Page 5 of 7
Report No.: AHEE230300050751
Test data table:
Test results
Measurement No.
Average energy consumption per hour (kW.h)
Average indoor room stable temp.
Appliance settings
‘ Cooling-16 ℃ -min wind speed ’ mode ‘ Cooling-16 ℃ -max wind speed ’ mode ‘ Cooling-26 ℃ -max wind speed ’ mode ‘ Cooling-26 ℃ -min wind speed ’ mode
1
0.505
18.8 ℃
2
0.672
17.6 ℃
3
0.081
25.0 ℃
4
0.189
26.2 ℃
TRF No. EEC_Protocol performance test A
Page 6 of 7
Report No.: AHEE230300050751
Test Details Description – Heating mode Model
AS12FBAHRA(indoor unit) + 1U12MEHFRA(outdoor unit)
Test voltage(V)/ Test frequency(Hz)
230 V, 50 Hz
EN14511-2: 2022/ Table 3: Heating Mode – Standard Rating Conditions Indoor Room Size: 22.34 mm 2 ; Installation Height of Indoor Unit: 2.3 m; Indoor Room Dry Bulb( ℃ )/Wet Bulb( ℃ ) : 20/--; Outdoor Room Dry Bulb( ℃ )/Wet Bulb( ℃ ) : 7/6
Test conditions
Measurement 5 Settings
Air conditioner is set to heating mode, the temperature is set to 20 ℃ , the wind speed is set to max.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Measurement 6 Settings
Air conditioner is set to heating mode, the temperature is set to 20 ℃ , the wind speed is set to min.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Measurement 7 Settings
Air conditioner is set to heating mode, the temperature is set to 30 ℃ , the wind speed is set to max.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Measurement 8 Settings
Air conditioner is set to heating mode, the temperature is set to 30 ℃ , the wind speed is set to min.
Test method
After the indoor side test room and walls reaching the setting temperature, the appliance is then operated continually for 5 hours, and record the values of power consumption per hour.
Test data
Details see below table
Set to ‘ Heating-20 ℃ - max wind speed ’ mode compared to 30 ℃ , can save the energy consumption 1.027 kwh per hour, the ration of fractional energy saving can up to 77%. Set to ‘ Heating-20 ℃ - min wind ’ speed mode compared to 30 ℃ , can save the energy consumption 0.809 kwh per hour, the ration of fractional energy saving can up to 78%.
Comparison of measurement 5&7
Conclusion
Comparison of measurement 6&8
TRF No. EEC_Protocol performance test A
Page 7 of 7
Report No.: AHEE230300050751
Test data table:
Test results
Measurement No.
Average energy consumption per hour (kW.h)
Average indoor room stable temp.
Appliance settings
‘ Heating-20 ℃ - max wind speed ’ mode ‘ Heating-20 ℃ - min wind speed ’ mode ‘ Heating-30 ℃ - max wind speed ’ mode ‘ Heating-30 ℃ - min wind speed ’ mode
5
0.313
21.2 ℃
6
0.231
20.2 ℃
7
1.34
26.5 ℃
8
1.04
24.5 ℃
-- End of Test Report --